Washington · Local jurisdiction reference

Everett Fire Code

Quick answer

Washington State Fire Code (2021 IFC as adopted in WAC 51-54A) with Everett amendments (EMC Chapter 16.03)

Fire code official (AHJ)
Everett Fire Department — Fire Marshal’s Office
Effective date
2024-03-15
Verification status
Checked against official sources · Last verified 2026-11-16

Local amendments & notes

Ordinance 4007-24 repealed and replaced EMC 16.03 to match the 2021 state fire code, timed to the delayed statewide effective date of March 15, 2024. Everett also adopts IFC appendices including B (fire flow), D (fire apparatus access) and E.

Inspection requirements by system in Everett

The schedules below are the national NFPA baseline that Everett’s adopted code references. Local amendments, the code edition your building was permitted under, occupancy, and AHJ interpretation can change them. New construction must meet the currently adopted code; existing buildings generally keep the systems they were approved with but must maintain them on the current inspection and testing schedule, unless a retroactive local requirement applies.

Fire sprinkler systems

NFPA 25 · NFPA 13 · Weekly through 5-Year

NFPA 25 sets inspection, testing, and maintenance for sprinkler systems, standpipes, fire pumps, private hydrants, and water tanks. Typical cycle: weekly or monthly valve and gauge checks, quarterly or semiannual waterflow alarm tests, an annual main drain test and control valve operation, a 3-year full-flow dry-pipe trip test, and 5-year internal pipe and standpipe work.

Fire alarm systems

NFPA 72 · Semiannual + Annual

Under NFPA 72 Chapter 14, most fire alarm initiating devices, notification appliances, and control equipment are functionally tested annually, with visual inspections from weekly to annually depending on the component and whether the system is monitored. Smoke detector sensitivity is checked within 1 year of installation, then every other year; after the second passing test the interval may extend to a maximum of 5 years.

Fire extinguishers

NFPA 10 · Monthly + Annual

NFPA 10 requires portable fire extinguishers to be inspected about every 30 days, maintained annually by a certified technician, and hydrostatically tested every 5 or 12 years depending on type. Stored-pressure units on a 12-year hydrostatic cycle, such as most dry-chemical extinguishers, also get a 6-year internal examination.

Commercial kitchen suppression

NFPA 96 · Semiannual

NFPA 96 requires a commercial kitchen’s fire-extinguishing system to be inspected and serviced at least every 6 months, with fusible-link detectors replaced at least semiannually per NFPA 17A. Exhaust hoods and ducts are inspected and cleaned monthly to annually depending on cooking volume, from monthly for solid-fuel cooking to annually for low-volume kitchens.

Fire pumps

NFPA 20 · NFPA 25 · Weekly/Monthly + Annual

NFPA 20 governs how stationary fire pumps are installed; their ongoing testing is in NFPA 25 Chapter 8. Diesel pumps run a no-flow (churn) test weekly for at least 30 minutes. Electric pumps run at least 10 minutes weekly, or monthly where NFPA 25 permits. Every pump gets an annual flow test at no flow, 100%, and 150% of rated capacity.

Emergency lighting & exit signs

NFPA 101 · Monthly + Annual

NFPA 101 Section 7.9 requires battery-powered emergency lighting and illuminated exit signs to be functionally tested for at least 30 seconds every month and for 1½ hours once a year, with written records. Self-testing or computer-based systems may follow alternative test provisions in the same section.

Full interval tables with edition and section: sprinkler (NFPA 25) · fire alarm (NFPA 72) · extinguishers (NFPA 10) · kitchen hood (NFPA 96) · build a 12-month calendar

Permits, plan review and inspections

Fire protection permits, plan review, acceptance testing and annual inspection reporting in Everett go through Everett Fire Department — Fire Marshal’s Office. Procedures and fees are set locally — use the official sources below for current forms and filing requirements. We do not publish local procedures we have not verified.

Frequently asked questions

What fire code applies in Everett, WA?

Washington State Fire Code (2021 IFC as adopted in WAC 51-54A) with Everett amendments (EMC Chapter 16.03). It took effect 2024-03-15.

Who enforces the fire code in Everett?

Everett Fire Department — Fire Marshal’s Office. Plan review, permits, acceptance tests and inspections are handled by that office; confirm which authority covers your parcel.

How often do fire alarm, sprinkler and extinguisher systems need inspection in Everett?

Inspection, testing and maintenance frequencies come from the NFPA standards the local code references (NFPA 72 for fire alarm, NFPA 25 for sprinklers and fire pumps, NFPA 10 for extinguishers, NFPA 96 for kitchen exhaust). Local amendments can add to them — see the system sections on this page.

Sponsor · Fire Solutions NWNeed inspection, testing or deficiency repair in Everett? Fire Solutions NW is licensed in Washington.Request a quote
Accuracy & verification

Local fire codes change by ordinance and may differ by building, permit date, and occupancy. This page is a published summary for general reference. Confirm requirements with Everett Fire Department — Fire Marshal’s Office before making compliance decisions.