2022 New York City Fire Code (NYC Administrative Code Title 29, enacted by Local Law 47 of 2022)
New York City writes its own fire code instead of using the Fire Code of New York State. The 2022 code came out of FDNY’s review of the 2012 and 2015 IFC plus selected 2018 IFC provisions. It applies to new and existing buildings as set out in FC102, and FDNY rules (3 RCNY) add filing and approval procedures — for example for fire alarm systems.
Applies in all five boroughs; FDNY enforces the NYC Fire Code.
State baseline: 2025 Fire Code of New York State, based on the 2024 IFC (Uniform Code, 19 NYCRR) (in effect since 2025-12-31). New York City applies that baseline and adds the local amendments above.
Educational summary of the official pages linked. Confirm current procedures with FDNY — Bureau of Fire Prevention.
The schedules below are the national NFPA baseline that New York City’s adopted code references. Local amendments, the code edition your building was permitted under, occupancy, and AHJ interpretation can change them. New construction must meet the currently adopted code; existing buildings generally keep the systems they were approved with but must maintain them on the current inspection and testing schedule, unless a retroactive local requirement applies.
NFPA 25 sets inspection, testing, and maintenance for sprinkler systems, standpipes, fire pumps, private hydrants, and water tanks. Typical cycle: weekly or monthly valve and gauge checks, quarterly or semiannual waterflow alarm tests, an annual main drain test and control valve operation, a 3-year full-flow dry-pipe trip test, and 5-year internal pipe and standpipe work.
Under NFPA 72 Chapter 14, most fire alarm initiating devices, notification appliances, and control equipment are functionally tested annually, with visual inspections from weekly to annually depending on the component and whether the system is monitored. Smoke detector sensitivity is checked within 1 year of installation, then every other year; after the second passing test the interval may extend to a maximum of 5 years.
NFPA 10 requires portable fire extinguishers to be inspected about every 30 days, maintained annually by a certified technician, and hydrostatically tested every 5 or 12 years depending on type. Stored-pressure units on a 12-year hydrostatic cycle, such as most dry-chemical extinguishers, also get a 6-year internal examination.
NFPA 96 requires a commercial kitchen’s fire-extinguishing system to be inspected and serviced at least every 6 months, with fusible-link detectors replaced at least semiannually per NFPA 17A. Exhaust hoods and ducts are inspected and cleaned monthly to annually depending on cooking volume, from monthly for solid-fuel cooking to annually for low-volume kitchens.
NFPA 20 governs how stationary fire pumps are installed; their ongoing testing is in NFPA 25 Chapter 8. Diesel pumps run a no-flow (churn) test weekly for at least 30 minutes. Electric pumps run at least 10 minutes weekly, or monthly where NFPA 25 permits. Every pump gets an annual flow test at no flow, 100%, and 150% of rated capacity.
NFPA 101 Section 7.9 requires battery-powered emergency lighting and illuminated exit signs to be functionally tested for at least 30 seconds every month and for 1½ hours once a year, with written records. Self-testing or computer-based systems may follow alternative test provisions in the same section.
Full interval tables with edition and section: sprinkler (NFPA 25) · fire alarm (NFPA 72) · extinguishers (NFPA 10) · kitchen hood (NFPA 96) · build a 12-month calendar
These national guides cover the findings inspectors write up most often. New York City-specific violation data is not published here.
Fire protection permits, plan review, acceptance testing and annual inspection reporting in New York City go through FDNY — Bureau of Fire Prevention. Procedures and fees are set locally — use the official sources below for current forms and filing requirements. We do not publish local procedures we have not verified.
2022 New York City Fire Code (NYC Administrative Code Title 29, enacted by Local Law 47 of 2022). It took effect 2022-04-15.
FDNY — Bureau of Fire Prevention. Plan review, permits, acceptance tests and inspections are handled by that office; confirm which authority covers your parcel.
Inspection, testing and maintenance frequencies come from the NFPA standards the local code references (NFPA 72 for fire alarm, NFPA 25 for sprinklers and fire pumps, NFPA 10 for extinguishers, NFPA 96 for kitchen exhaust). Local amendments can add to them — see the system sections on this page.
Inspection, testing and maintenance of extinguishing, standpipe, fire alarm and hydrant systems must be personally performed by an FDNY Certificate of Fitness holder who also holds, or works under, the required license (FC 901.6.3). Records of all required inspections, tests and maintenance are kept as required by FC 901.6.2 and FC 107.7. No routine report filing portal or filing fee was found.
Summaries are in our own words; NFPA and ICC text is copyrighted and is not reproduced here.
Local fire codes change by ordinance and may differ by building, permit date, and occupancy. This page is a published summary for general reference. Confirm requirements with FDNY — Bureau of Fire Prevention before making compliance decisions.