California · Local jurisdiction reference

San Diego Fire Code

Quick answer

2025 California Fire Code with portions of the 2024 IFC (Appendices B, C, D), plus city amendments

Fire code official (AHJ)
San Diego Fire-Rescue Department — Fire Prevention Bureau
Effective date
2026-01-01
Verification status
Checked against official sources · Last verified 2026-11-15

Local amendments & notes

Local amendments to the CFC are adopted in the San Diego Municipal Code (Chapter 5, Article 5, Division 83).

Inspection requirements by system in San Diego

The schedules below are the national NFPA baseline that San Diego’s adopted code references. Local amendments, the code edition your building was permitted under, occupancy, and AHJ interpretation can change them. New construction must meet the currently adopted code; existing buildings generally keep the systems they were approved with but must maintain them on the current inspection and testing schedule, unless a retroactive local requirement applies.

Fire sprinkler systems

NFPA 25 · NFPA 13 · Weekly through 5-Year

NFPA 25 sets inspection, testing, and maintenance for sprinkler systems, standpipes, fire pumps, private hydrants, and water tanks. Typical cycle: weekly or monthly valve and gauge checks, quarterly or semiannual waterflow alarm tests, an annual main drain test and control valve operation, a 3-year full-flow dry-pipe trip test, and 5-year internal pipe and standpipe work.

Fire alarm systems

NFPA 72 · Semiannual + Annual

Under NFPA 72 Chapter 14, most fire alarm initiating devices, notification appliances, and control equipment are functionally tested annually, with visual inspections from weekly to annually depending on the component and whether the system is monitored. Smoke detector sensitivity is checked within 1 year of installation, then every other year; after the second passing test the interval may extend to a maximum of 5 years.

Fire extinguishers

NFPA 10 · Monthly + Annual

NFPA 10 requires portable fire extinguishers to be inspected about every 30 days, maintained annually by a certified technician, and hydrostatically tested every 5 or 12 years depending on type. Stored-pressure units on a 12-year hydrostatic cycle, such as most dry-chemical extinguishers, also get a 6-year internal examination.

Commercial kitchen suppression

NFPA 96 · Semiannual

NFPA 96 requires a commercial kitchen’s fire-extinguishing system to be inspected and serviced at least every 6 months, with fusible-link detectors replaced at least semiannually per NFPA 17A. Exhaust hoods and ducts are inspected and cleaned monthly to annually depending on cooking volume, from monthly for solid-fuel cooking to annually for low-volume kitchens.

Fire pumps

NFPA 20 · NFPA 25 · Weekly/Monthly + Annual

NFPA 20 governs how stationary fire pumps are installed; their ongoing testing is in NFPA 25 Chapter 8. Diesel pumps run a no-flow (churn) test weekly for at least 30 minutes. Electric pumps run at least 10 minutes weekly, or monthly where NFPA 25 permits. Every pump gets an annual flow test at no flow, 100%, and 150% of rated capacity.

Emergency lighting & exit signs

NFPA 101 · Monthly + Annual

NFPA 101 Section 7.9 requires battery-powered emergency lighting and illuminated exit signs to be functionally tested for at least 30 seconds every month and for 1½ hours once a year, with written records. Self-testing or computer-based systems may follow alternative test provisions in the same section.

Full interval tables with edition and section: sprinkler (NFPA 25) · fire alarm (NFPA 72) · extinguishers (NFPA 10) · kitchen hood (NFPA 96) · build a 12-month calendar

Permits, plan review and inspections

Fire protection permits, plan review, acceptance testing and annual inspection reporting in San Diego go through San Diego Fire-Rescue Department — Fire Prevention Bureau. Procedures and fees are set locally — use the official sources below for current forms and filing requirements. We do not publish local procedures we have not verified.

Frequently asked questions

What fire code applies in San Diego, CA?

2025 California Fire Code with portions of the 2024 IFC (Appendices B, C, D), plus city amendments. It took effect 2026-01-01.

Who enforces the fire code in San Diego?

San Diego Fire-Rescue Department — Fire Prevention Bureau. Plan review, permits, acceptance tests and inspections are handled by that office; confirm which authority covers your parcel.

How often do fire alarm, sprinkler and extinguisher systems need inspection in San Diego?

Inspection, testing and maintenance frequencies come from the NFPA standards the local code references (NFPA 72 for fire alarm, NFPA 25 for sprinklers and fire pumps, NFPA 10 for extinguishers, NFPA 96 for kitchen exhaust). Local amendments can add to them — see the system sections on this page.

Sources

Summaries are in our own words; NFPA and ICC text is copyrighted and is not reproduced here.

Sponsor · Fire Solutions NWNeed inspection, testing or deficiency repair in San Diego? Fire Solutions NW is licensed in California.Request a quote
Accuracy & verification

Local fire codes change by ordinance and may differ by building, permit date, and occupancy. This page is a published summary for general reference. Confirm requirements with San Diego Fire-Rescue Department — Fire Prevention Bureau before making compliance decisions.