6 Critical Fire Protection Items for Your New Construction Punch List

Published by The Fire Code Authority·Updated November 8, 2026·6 items

Final fire protection acceptance is frequently where new commercial construction projects stall — not because the systems don't work, but because the documentation, labels, or acceptance tests weren't completed. These six items show up on close to every punch list for a reason.

  1. 1

    NFPA 13 Contractor's Material and Test Certificate (Form 28.3.1)

    The fire sprinkler contractor must complete and submit the NFPA 13 Material and Test Certificate, signed by the installer and a witness. Without this document the AHJ will not sign off on occupancy. Owners rarely know to ask for it.

    📖 NFPA 13 §28.3.1
  2. 2

    NFPA 72 Record of Completion and 100% Device Test

    Fire alarm acceptance requires 100% functional test of every initiating device, notification appliance, and relay, documented on the NFPA 72 Record of Completion. Verify the test was performed by the installer witnessed by the AHJ.

    📖 NFPA 72 §7.5
  3. 3

    As-Built Drawings Delivered to Owner AND AHJ

    Record drawings showing actual installed sprinkler layout, alarm device locations, and equipment identification must be delivered at completion. Many jurisdictions require a copy posted inside the fire riser room.

    📖 NFPA 13 §28.3.4
  4. 4

    Hydraulic Nameplate at Each Riser

    Each sprinkler riser must have a permanent metal nameplate showing design area, density, and hose stream allowance. Missing nameplates = immediate NFPA 25 finding at the first annual inspection.

    📖 NFPA 13 §7.1.2
  5. 5

    Fire Pump Acceptance Test Documentation (If Applicable)

    New fire pumps require a formal acceptance test — flow test at 100%, 150%, and churn — witnessed by the AHJ and documented. Common punch-list miss on buildings that took final occupancy before the test was completed.

    📖 NFPA 20 §14.2
  6. 6

    System Impairment Procedures Posted at Riser

    The sprinkler riser room must have posted procedures for system impairment: who to call, central station contact, fire watch procedures. Often skipped on new construction and missed at first inspection.

    📖 NFPA 25 §15.3

In Summary

New construction fire protection acceptance is a documentation exercise as much as a systems exercise. The building owner who makes these six items a specific closeout checklist — handed to the GC and the fire protection subcontractor at the start — eliminates the usual post-occupancy punch-list fire drill.

Reference Only
Published summary for informational use. Fire code adoption varies by jurisdiction and edition. Verify current enforced codes with your local Authority Having Jurisdiction (AHJ) and consult a licensed fire protection contractor before taking action. Not legal or professional advice.